TEMPEST \ TR75-12A

Tempest TR75-12A

Nominal Voltage

12V

Rated Capacity (20 hour rate)

75AH

Dimension

Total Height
(with terminals)

9.20 in

Height

8.03 in

Length

10.21 in

Width

6.60 in

Weight (Approx)

62.17 lbs

Capacity
(77oF/25oC)

20 hour rate (3.75A)

75AH

10 hour rate (6.98A)

69.8AH

5 hour rate (12.75A)

63.8AH

1 hour rate (45A)

45AH

15 min. rate (131.2A)

32.8AH

Internal Resistance

Fully Charged 77oF/25oC

5mW

Capacity Affected by Temperature
(77oF/25oC)

104°F (40°C)

102%

77°F (25°C)

100%

32°F (0°C)

85%

5°F (-15°C)

65%

Self Discharge
(77oF/25oC)

Capacity after 3 month storage

91%

Capacity after 6 month storage

82%

Capacity after 12 month storage

64%

Max. Discharge Current
(77oF/25oC)

1125A (5S)

Terminal

Standard

F5

Optional

 

Charging (Constant Voltage)

Cycle

Initial Charging Current 15A (recommended)
14.5~14.9V/ 77°F (25°C)

Float

13.6~13.8V/77°F (25°C)

Cut-Off Voltage

30min

1 hr

3 hr

5 hr

12 hr

24 hr

1.60V

172

96.8

39.3

26.4

12.5

6.43

1.65V

171

95.9

39.0

26.4

12.5

6.43

1.70V

165

94.3

38.3

26.4

12.5

6.43

1.75V

159

92.7

37.9

26.0

12.5

6.43

1.80V

153

91.2

37.4

25.6

12.3

6.43

| Back |