TEMPEST \ TR12-12

Tempest TR12-12

Nominal Voltage

12 V

Rated Capacity (20 hour rate)

12AH

Dimension

Total Height
(with terminals)

3.98 in

Height

3.74 in

Length

5.94 in

Width

3.90 in

Weight (Approx)

8.26 lbs

Capacity
(77oF/25oC)

20 hour rate (600mA)

12AH

10 hour rate (1.12A)

11.2AH

5 hour rate (2.04A)

10.2AH

1 hour rate (7.2A)

7.2AH

15 min. rate (21A)

5.25AH

Internal Resistance

Fully Charged 77oF/25oC

14mW

Capacity Affected by Temperature
(77oF/25oC)

104°F (40°C)

102%

77°F (25°C)

100%

32°F (0°C)

85%

5°F (-15°C)

65%

Self Discharge
(77oF/25oC)

Capacity after 3 month storage

91%

Capacity after 6 month storage

82%

Capacity after 12 month storage

64%

Max. Discharge Current
(77oF/25oC)

180A (5S)

Terminal

Standard

F2

Optional

F1

Charging (Constant Voltage)

Cycle

Initial Charging Current 2.4A (recommended)
14.5~14.9V/ 77°F (25°C)

Float

13.6~13.8V/77°F (25°C)

Cut-Off Voltage

5min

10min

15min

30min

40min

60min

1.50V

84.4

57.4

45.0

27.5

23.5

16.3

1.60V

82.4

56.6

43.9

26.7

22.5

15.9

1.67V

80.7

55.3

43.0

26.2

22.1

15.6

1.70V

79.5

54.1

41.9

25.6

21.8

15.5

1.75V

76.3

52.5

40.5

24.9

21.3

15.1

| Back |