TEMPEST \ TR35-12

U1 35

Nominal Voltage

12 V

Rated Capacity (20 hour rate)

35AH

Dimension

Total Height
(with terminals)

6.57 in

Height

6.10 in

Length

7.72 in

Width

5.16 in

Weight (Approx)

25.35 lbs

Capacity
(77oF/25oC)

20 hour rate (1.75A)

35AH

10 hour rate (3.26A)

32.6AH

5 hour rate (5.96A)

29.8AH

1 hour rate (21A)

21AH

15 min. rate (61.24A)

15.31AH

Internal Resistance

Fully Charged 77oF/25oC

9mW

Capacity Affected by Temperature
(77oF/25oC)

104°F (40°C)

102%

77°F (25°C)

100%

32°F (0°C)

85%

5°F (-15°C)

65%

Self Discharge
(77oF/25oC)

Capacity after 3 month storage

91%

Capacity after 6 month storage

82%

Capacity after 12 month storage

64%

Max. Discharge Current
(77oF/25oC)

525A (5S)

Terminal

Standard

F15

Optional

F5

Charging (Constant Voltage)

Cycle

Initial Charging Current 7A (recommended)
14.5~14.9V/ 77°F (25°C)

Float

13.6~13.8V/77°F (25°C)

Cut-Off Voltage

30min

1 Hr

3 Hr

5 Hr

12 Hr

24 Hr

1.60V

86.8

53.1

21.6

14.5

6.55

3.35

1.65V

86.6

52.4

21.3

14.5

6.55

3.35

1.70V

83.3

51.2

20.8

14.5

6.55

3.35

1.75V

81.7

50.3

20.6

14.2

6.55

3.35

1.80V

80.1

49.4

20.4

14.0

6.50

3.35

| Back |